# Chapter 11 Withstand current = $I_{sc}$ $Z_{thev} = {V_{nominal} \over I_{sc}}$ ## Dual Voltage Transformers usually single phase usually residential Medium voltage primary Secondary is (2) 120V secondaries. There’s 3 wires. One thats bare wire (neutral), and 2 wires for power, both at 120V. Just like the transformer that we used in lab. The transmission lines generally go to multiple households. This makes it easier to balance the load. Large buildings normally have $208V_{line}$, or $120V$ in a 3-phase, wye power. ![](2-24_Notes.assets/redundancyConnection.png) ![](2-24_Notes.assets/highCurrentTransformer.png) ## Autotransformers ![](2-24_Notes.assets/autoTransformer.png) Primary turns $N_p$ Secondary turns ($N_s$) $V_s=\frac{N_s}{N_p}\times V_p$ Turns ratio $a=\frac{N_s}{N_p}$ $I_pN_p=I_sN_s$ $I_p$ and $I_s$ are both down There’s a problem: Theres no isolation between the primary and the secondary. Its cheaper, but noise problems are still there. They’re normally labeled, but our professor is an asshole, so we don’t know in lab. Don’t use a nail as a fuse. # Chapter 12: 3-Phase It… its just 3 transformers ## Delta-Wye configuration ![](2-24_Notes.assets/3phaseTransformerDeltaWye.png) Left is $\Delta$, right is $Y$ Name-plate: $480-208$ = $\Delta-\Delta$ $480/277-208/120$=$Y-Y$ These can be in any combination