1.9 KiB
Skyler MacDougall
Homework 12: due 4/8/2020
-
In analyzing a hydropower site, it is found that the turbines should turn at close to 350r/min. If the directly coupled generators must generate a frequency of 60Hz, calculate the following:
- The number of poles on the rotor
- The exact turbine speed
-
An isolated 3-phase generator produces a no-load line voltage of 13.2kV. If a load having a lagging power factor of 0.8 is connected to the machine, must the excitation be increased or decreased in order to maintain the same line voltage?
-
What conditions must be met before a generator can be connected to a 3-phase system?
-
Calculate the number of poles on the generator in figure 12 below using the information given.
-
Calculate the number of poles on the aircraft generator shown in the figure 11 below.
-
The 3-phase generator shown in the figure 16 below has the following characteristics:
E_o=2440V\ X_s=144\Omega\ R=17\Omega\ Z=175\Omega (resistive)
Calculate
- The synchronous impedance
Z_s
per phase - The total resistance of the circuit per phase
- The total reactance of the circuit per phase
- the line current
- the line-to-neutral voltage across the load
- the line voltage across the load
- the power of the turbine driving the alternator
- the phase angle between
E_o
and the voltage across the load
- The synchronous impedance
-
Referring to the figure 17 below, the following information is given about the generator:
E_o=12kV\ E=14kV\ X_s=2\Omega\ E_o\ leads\ E\ by\ 30^\circ
- calculate the total active power output of the generator
- draw the phasor diagram for one phase
- calculate the power factor of the load