eeet-242/lab1.md

5.2 KiB
Raw Permalink Blame History

Objective

The objective of this lab was to study the relationship between voltage and current in wye and delta 3-phase circuits, as well as to determine the real, apparent, and reactive power in said circuits.

Wiring Diagram

Part 1

wiringDiagramPart1

Part 2

wiringDiagramPart2

Part 3

wiringDiagramPart3

Procedure

Part 1

  1. Connect the above wye circuit using the resistance and meter modules. DO NOT connect to the neutral.
  2. Set each resistance to 400\Omega per phase. Use ohmmeter to measure the phase resistance (including the connecting cables).
  3. Turn on the power supply and adjust for 208V_{AC} line voltage.
  4. Measure and record the voltages across the current through the 3 load resistors.
  5. Calculate the total power delivered to the three loads.

Part 2

  1. Connect the delta circuit shown above.
  2. Set each resistance to 400\Omega. Before turning on the power suppluy, call the instructor or the TA to inspect your connections.
  3. Turn on the power supply and adjust for 120V _{AC} line voltage.
  4. Measure and record the line voltages.
  5. Calculate, using measured data, the total 3-phase power.

Part 3

  1. Connect the above wye circuit shown below. DO NOT connect the neutral.
  2. Set each resistance to 400\Omega and each inductance to 0.8H.
  3. Turn the power supply on and adjust for 208V_{AC}.
  4. Measure and record the line currents and the voltages across each inductive load.
  5. Measure and record the voltages across each resistor.
  6. Using measured date, calculate the real power on each load.
  7. Calculate the total 3-phase real power, the reactive power in each load, the total 3-phase reactive power, the total 3-phase apparent power and the power factor.

Experimental Data

Part 1

Phase Measured Resistance (\Omega) Line Currents (A) Load Voltage (V) Per \phi Power (W)
1 415 0.34 120 40.8
2 413 0.35 120 42.0
3 414 0.34 120 40.8

Total Three-phase power: 123.6W

Part 2

Phase Resistance (\Omega) Currents (A) Per \phi Power (W)
1 400 0.5 100
2 400 0.6 144
3 400 0.55 121

Total three-phase power: 365W

Part 3

Phase Measured Current(A) Inductive Voltage(V) Resistive Voltage(V)
1 0.25 67.5 89
2 0.26 67.5 89
3 0.25 67.5 89
Phase Real Power (W) Reactive Power (VAR) Apparent Power(VA) Power Factor
1 22.25 16.875 27.9 0.80
2 23.14 17.550 29.0 0.80
3 22.00 16.875 27.7 0.79

Three Phase Real Power: 67.39W

Three Phase Reactive Power:$51.625VAR$

Three Phase Apparent Power:$84.6VA$

Power Factor: 0.80

Calculations and Analysis

Power Calculation: Part 1

R_{theory}=400\Omega; I_{in}=0.34\overline3A\ P=I^2R=(0.34\overline3A)^2(400\Omega)\ P=47W\ P_{total}=141W

Power Calculation: Part 2

P=I^2R; R=400\Omega; I=0.5A;\ P=(0.5A)^2\times 400\Omega\ P=100W\

Power Calculation: Part 3

P=IV;\hspace{2mm}Q=IV_{reactive} I=0.25A;\hspace{2mm} V_1=67.5V\angle90^\circ; \hspace{2mm} V_2=89V\angle0^\circ\ Q_1=0.25A\times 67.5V_{reactive}; P_1=0.25A\times89V\ Q_1=16.875VAR; P_1=22.25W\ S=\sqrt{P^2+Q^2}\ S=\sqrt{(22.25W)^2+(16.875VAR)^2}\ S\approx27.9VA\ pf={P\over S}={22.25W\over 27.9VA}\ pf=0.80

Questions

  1. Redo the calculations in part 1 with the ideal resistances of 400\Omega. How do these results compare to the actual? If the values are different, explain the differences.

R_{avg_{meas}}=414\Omega\ I_{avg_{meas}}=0.34\overline{3}A\ P_{avg_{meas}}=44.8W\ P_{total_{meas}}=146W

These numbers are within error of the measured values.

Results and Conclusions

All of our results were within error. They werent exactly the same, because of tolerances and impurities.

For part 1 of the lab, we had a three phase power of 123.6W. For part 2 of the lab, we had a three phase power of 365W. For part 3 of the lab, we had 84.6VA \ at \ 0.80pf.