Objective
The objective of this lab was to study the relationship between voltage and current in wye and delta 3-phase circuits, as well as to determine the real, apparent, and reactive power in said circuits.
Wiring Diagram
Part 1
Part 2
Part 3
Procedure
Part 1
- Connect the above wye circuit using the resistance and meter modules. DO NOT connect to the neutral.
- Set each resistance to
400\Omega
per phase. Use ohmmeter to measure the phase resistance (including the connecting cables). - Turn on the power supply and adjust for
208V_{AC}
line voltage. - Measure and record the voltages across the current through the 3 load resistors.
- Calculate the total power delivered to the three loads.
Part 2
- Connect the delta circuit shown above.
- Set each resistance to
400\Omega
. Before turning on the power suppluy, call the instructor or the TA to inspect your connections. - Turn on the power supply and adjust for
120V _{AC}
line voltage. - Measure and record the line voltages.
- Calculate, using measured data, the total 3-phase power.
Part 3
- Connect the above wye circuit shown below. DO NOT connect the neutral.
- Set each resistance to
400\Omega
and each inductance to0.8H
. - Turn the power supply on and adjust for
208V_{AC}
. - Measure and record the line currents and the voltages across each inductive load.
- Measure and record the voltages across each resistor.
- Using measured date, calculate the real power on each load.
- Calculate the total 3-phase real power, the reactive power in each load, the total 3-phase reactive power, the total 3-phase apparent power and the power factor.
Experimental Data
Part 1
Phase | Measured Resistance (\Omega ) |
Line Currents (A ) |
Load Voltage (V ) |
Per \phi Power (W ) |
---|---|---|---|---|
1 | 415 | 0.34 | 120 | 40.8 |
2 | 413 | 0.35 | 120 | 42.0 |
3 | 414 | 0.34 | 120 | 40.8 |
Total Three-phase power: 123.6W
Part 2
Phase | Resistance (\Omega ) |
Currents (A ) |
Per \phi Power (W ) |
---|---|---|---|
1 | 400 | 0.5 | 100 |
2 | 400 | 0.6 | 144 |
3 | 400 | 0.55 | 121 |
Total three-phase power: 365W
Part 3
Phase | Measured Current(A ) |
Inductive Voltage(V ) |
Resistive Voltage(V ) |
---|---|---|---|
1 | 0.25 | 67.5 | 89 |
2 | 0.26 | 67.5 | 89 |
3 | 0.25 | 67.5 | 89 |
Phase | Real Power (W ) |
Reactive Power (VAR ) |
Apparent Power(VA ) |
Power Factor |
---|---|---|---|---|
1 | 22.25 | 16.875 | 27.9 | 0.80 |
2 | 23.14 | 17.550 | 29.0 | 0.80 |
3 | 22.00 | 16.875 | 27.7 | 0.79 |
Three Phase Real Power: 67.39W
Three Phase Reactive Power:$51.625VAR$
Three Phase Apparent Power:$84.6VA$
Power Factor: 0.80
Calculations and Analysis
Power Calculation: Part 1
R_{theory}=400\Omega; I_{in}=0.34\overline3A\
P=I^2R=(0.34\overline3A)^2(400\Omega)\
P=47W\
P_{total}=141W
Power Calculation: Part 2
P=I^2R; R=400\Omega; I=0.5A;\
P=(0.5A)^2\times 400\Omega\
P=100W\
Power Calculation: Part 3
P=IV;\hspace{2mm}Q=IV_{reactive} I=0.25A;\hspace{2mm} V_1=67.5V\angle90^\circ; \hspace{2mm} V_2=89V\angle0^\circ\
Q_1=0.25A\times 67.5V_{reactive}; P_1=0.25A\times89V\
Q_1=16.875VAR; P_1=22.25W\
S=\sqrt{P^2+Q^2}\
S=\sqrt{(22.25W)^2+(16.875VAR)^2}\
S\approx27.9VA\
pf={P\over S}={22.25W\over 27.9VA}\
pf=0.80
Questions
- Redo the calculations in part 1 with the ideal resistances of
400\Omega
. How do these results compare to the actual? If the values are different, explain the differences.
R_{avg_{meas}}=414\Omega\
I_{avg_{meas}}=0.34\overline{3}A\
P_{avg_{meas}}=44.8W\
P_{total_{meas}}=146W
These numbers are within error of the measured values.
Results and Conclusions
All of our results were within error. They weren’t exactly the same, because of tolerances and impurities.
For part 1 of the lab, we had a three phase power of 123.6W
. For part 2 of the lab, we had a three phase power of 365W
. For part 3 of the lab, we had 84.6VA \ at \ 0.80pf
.